Description
  • Digital single-phase power meter with built-in cut-off relay for independent telemanagement of up to 2 single-phase lines.
  • Internal memory for Modbus (RTU) registers and communications.
  • Direct measurement 10 (65) A.
  • The cut-off relay is an independent-per-phase and can be programmed for backward and forward scheduling of consumption (kWh), time, etc.
  • This feature is ideal for consumer management or prepaid installations such as campsites, rents or others.
  • Load curve of 9,000 depth information. It corresponds to 3 months with integration every 15 min.
  • Independent recording of import and export data for energy-generating installations, solar installations, etc.
  • Up to 6 daily periods with 4 possible tariffs.
  • It distinguishes between Monday-Friday, Saturday, Sunday and public holidays. Winter and Summer season
  • Upper limit register: V, A, Wh y VArh
  • Power cut register.
  • 12 monthly closures: Wh import/export and VArh import/export.
  • Load curve of V, A, Wh y VArh. It is configurable every 15, 30 and 60 minutes
  • Reading on the LCD display of the following instantaneous parameters. V, A, W, VAr, VA, cos and Hz
  • Opto-isolated pulse output or RS485 communications.
  • LED indicators: active consumption, reactive consumption, memory error, phase sequence error, and phase error
  • 10-year memory backup by lithium battery.
  • Accessories: USB-RS485 adapter (OB707022) and MODBUS/TCP gateway (OB709972).
    Models
    • Model: CONTAX D-6593 BUS-R V 3x1
    • Reference
      OB709400V3
Technical specifications
  • Supply voltage:
    230 V ac (-20% to +15%), 50-60 Hz
  • Base and maximum current:
    10 (65) A
  • Start current:
    of 40 mA
  • Max. own consumption:
    1 VA
  • Accuracy active class
    1 according to UNE-EN 62053-21
  • Accuracy reactive class
    2 according to UNE-EN 62053-23
  • RS485
    serial port
  • MODBUS
    communication protocol
  • Type of codification:
    RTU (Remote Terminal Unit)
  • Communications:
    S0 pulses according to EN 62053-31
  • Active constant:
    800 imp/kWh
  • Reactive constant:
    800 imp/kWh
  • Operating Temp:
    from -25 ºC to +55 ºC
  • Protection degree:
    IP 20 according to EN 60529
  • Mounted
    on DIN rail according to EN 60715
  • Width module:
    9
Documentation and downloads