Description
  • Suspended ceiling recessed mounted (65 mm hole).
  • Unobtrusive design in polished white finish with high detection flat lens.
  • Basic functions cover most applications.
  • Outside temperature compensation provides more precise detection.
  • Dual neutral connection terminal for easier installation.
  • Adjustable parameters: timing and light sensitivity.
  • Detection field limiter included, which allows detection cancelation in specific points within thedetection area.
  • Includes zero-crossing detection feature, required for LED, fluorescence or low energy lighting load control, etc.
  • Ideal for installation in landings, halls, bathroom facilities, sanitary cabins, etc.
    • Models:
      • Model: DICROMAT + 230 V ac 50 Hz
      • Reference
        OB136112
      • Aplicaciones
        Landings, halls, bathroom facilities, sanitary cabins, etc.
        Model: DICROMAT + 120/230 V ac 50/60 Hz
      • Reference
        OB136100
      • Aplicaciones
        Landings, halls, bathroom facilities, sanitary cabins, etc.
    Technical specifications
    • Power supply: 230 V ac ± 10 %.
    • Nominal frequency: 50 Hz.
    • Power consumption: 5,5 VA (0,8 W).
    • Switching capacity: µ 6 A / 230 V~ cosφ = 1.
    • Detection angle: 360º.
    • Detection field: Up to 10 m diameter at 2,5 m height.
    • Brightness range: 3 to 2000 lux.
    • Timing range: 10 s to 15 min.
    • Degree of protection: IP 20 according to EN 60529.
    • Operating temperature: -20 to +40 ºC.
    • Maximum recommended load :
      • Incandescent: 1200 W.
      • Fluorescent: 400 VA.
      • Low voltage halogen (12 V AC): 1000 VA.
      • Halogen (230 V AC): 1200.
      • Low consumption lamps: 500 VA.
      • Downlights: 500 VA.
      • LED: 500 VA.

    Features for 230 V ac. For other voltages, please contact us.